Before installing the module, become familiar with the Installation and Operation Guide for the control panel you are using. Install, test and maintain the module according to these instructions, NFPA codes, local codes, and the authority having jurisdiction AHJ. Failure to follow these instructions can result in failure of the device to operate properly. Bosch Security Systems, Inc.

A short on the bus causes activation of the isolators adjacent to either side of the short and their yellow status LEDs light steady. This effectively separates all devices between the activated isolators from the rest of the bus. This prevents failure of the entire bus. When the short condition is removed, the isolators automatically restore the entire loop to normal operation. The isolator module is compatible with the devices listed in the table.

All other isolators must be placed as close as possible, preferably within 6 in. Place additional pairs of isolators between every subsequent device on the MUX bus. The isolators are not placed between each device but are placed to protect groups of up to 25 devices see the following figure. More than one Class B device loop can be in the same zone. All the devices beyond the shorted section of the device loop will be disabled. The available device addresses are 9 to and no more than 25 devices can be on any one Class B branch.

Each Class B branch must be within a single zone. More than one Class B branch can be in the same zone. If a short occurs, all the devices between the isolators on either side of the short will be disabled. Secure the faceplate to the front of the module.

FIGURING THE JOY OF NUMBERS BY SHAKUNTALA DEVI PDF

Bosch FPD-7024 Operation And Installation Manual

Before installing the module, become familiar with the Installation and Operation Guide for the control panel you are using. Install, test and maintain the module according to these instructions, NFPA codes, local codes, and the authority having jurisdiction AHJ. Failure to follow these instructions can result in failure of the device to operate properly. Bosch Security Systems, Inc. A short on the bus causes activation of the isolators adjacent to either side of the short and their yellow status LEDs light steady. This effectively separates all devices between the activated isolators from the rest of the bus. This prevents failure of the entire bus.